Gem Equipments, Compressed Air & Cooling System

GEM Equipments Limited » Products »
Compact Refrigrated Air Dryers » 2KD Series Specifications

Back to Product Details
TECHNICAL SPECIFICATIONS
Base
Model
Model
Variance
Nominal Capacity @
Maximum
Pressure #
Electrical
Connection
Air
Connection
Rated Power *
B
D
cfm
m³/h
bar g
psi g
220V /
1Ø/50Hz
415V /
3Ø/50Hz
In / Out
Air
Cooled
Water
Cooled
2KD+ 002
20
34
16
232
½"BSP(F)
0.15
2KD+ 004
40
68
16
232
½"BSP(F)
0.20
2KD+ 006
60
102
16
232
1"BSP(F)
0.40
2KD+ 008
80
136
16
232
1"BSP(F)
0.50
2KD+ 010
100
170
16
232
1½"BSP(F)
0.60
2KD+ 015
150
255
16
232
1½"BSP(F)
0.90
2KD+ 020
200
340
16
232
1½"BSP(F)
1.20
2KD+ 025
250
425
16
232
2"BSP(F)
1.40
2KD+ 030
300
510
16
232
2"BSP(F)
1.60
2KD+ 040
400
680
16
232
2"BSP(F)
1.90
1.60
2KD+ 050
500
850
16
232
3"NB ASME Flg
2.30
1.90
2KD+ 060
600
1020
16
232
3"NB ASME Flg
2.80
2.30
2KD+ 075
750
1275
16
232
3"NB ASME Flg
3.80
3.00
2KD+ 100
1000
1700
16
232
4"NB ASME Flg
5.00
4.10
2KD+ 125
1250
2125
16
232
4"NB ASME Flg
5.70
4.80
2KD+ 150
1500
2550
12.5
180
5"NB ASME Flg
6.80
6.20
2KD+ 200
2000
3400
12.5
180
6"NB ASME Flg
8.70
8.00
2KD+ 250
2500
4100
12.5
180
6"NB ASME Flg
11.00
9.60

@ - Flow capacities in accordance with ISO 7183, air suction of FAD 20°C (68°F), 1 bar (14.5 psi) at the operating conditions mentioned below
# - Voltage range 200 to 240V for 1ø & 380 - 420V for 3ø
* - Rated power is the max power consumed at conditions as per ISO 7183 Option 2

NOTE: Above models are with Reciprocating type refrigeration compressors. For Scroll type compressors, please refer to GEM

Model Nomenclature :

 

SHIPPING DETAILS
Base Model
Machine Dimensions in mm
Net Weight in kg
Length (A)
Width (B)
Height (C)
2KD+ 002
360
425
500
45
2KD+ 004
360
425
500
47
2KD+ 006
450
550
610
80
2KD+ 008
450
550
610
85
2KD+ 010
700
700
830
120
2KD+ 015
700
700
830
130
2KD+ 020
700
700
830
140
2KD+ 025
900
900
1230
160
2KD+ 030
900
900
1230
160
2KD+ 040
900
900
1230
180
2KD+ 050
750
1000
1400
225
2KD+ 060
750
1000
1400
250
2KD+ 075
900
1200
1475
375
2KD+ 100
900
1200
1725
400
2KD+ 125
900
1200
1725
425
2KD+ 150
1300
1800
1650
650
2KD+ 200
1300
1800
1900
800
2KD+ 200
1300
1800
1900
850

Sizing Conversion Factors:

Inlet Temperature (C1)      
Temperature °C
30
35
40
45
50
55
60
Correction Factor
1.2
1.15
1.05
1.0
0.85
0.7
0.6

Ambient Temperature (C2)
Temparature
25
30
35
40
45
50
Correction factor
1.2
1.15
1.1
1.05
1.0
0.9

Inlet Pressure (C3)         
Inlet Pressure
bar (g)
4
5
6
7
8
9
10.5
11
12.5
13
14
15
16
psi (g)
58
73
87
100
116
131
150
160
180
189
200
218
232
Correction Factor
.
0.75
0.85
0.95
1.00
1.06
1.04
1.07
1.18
1.09
1.22
1.12
1.25
1.14

Dew Point (C4)             
Dewpoint in C
3
7
10
Correction Factor
1.0
1.15
1.3


Dryer Normal Capacity =   Actual Capacity × C4
C1 × C2 × C3

* Product Design and specification subject to change due to constant upgradation.

Back to Product Details
Home | Profile | Products | Quality | Sales & Service | Catalogues | Manuals | Contact |

Compressed Air Dryers | Compressed Air Treatment Accessories | Cooling Towers | Industrial Coolers
Go To Top
Copyright © 2007 Gem Equipments Limited. All Rights Reserved.
An Indiglow Presentation

 

s